8
Ratings
Each unit must meet the following specifications:
ARI rating of _________BTUH cooling (and _________
BTUH reverse cycle heating with a COP of _________ at
47° F O.D.)
Electric resistance heat of _________ BTUH. Total Amp
draw must be of _________ and _________ Watts at
_________ volts.
The unit must remove a minimum of _________ pints of
moisture per hour when operated at rating conditions. The
EER must be a minimum of _________ EER.
Unit Chassis
Each unit must be slide out design shipped with room
cabinet front installed. Unit chassis must have the ability to
be installed with zero clearance from finished floor. An
electrical power cord must be included with chassis and
installed by the manufacturer to assure proper NEMA 6 or 7
configuration and UL approved length. Unit must be tested
for conformance to ASTME water infiltration specification
ASTME 331-86 which ensures no water infiltration when
tested at 8 inches rain per hour at 63 mph wind for 15
minutes.
Room Cabinet
The front of the room cabinet must be able to be field
secured to chassis to inhibit tampering. Filter must be
accessible without removing room front. Cabinet depth must
not exceed 7” to minimize unit’s impact on room space.
Heat Pumps
Each unit must include a changeover thermostat that senses
an outside coil switch-over temperature of 25° Fahrenheit,
lock-open refrigerant reversing valve during heat pump
operation, temperature-activated defrost drain and auto-
matic emergency heat operation to override the heat pump’s
change-over thermostat and bring on electric resistance
heaters in the event of a sealed system failure. Unit must not
operate compressor and electric heaters simultaneously.
Compressor
The compressor must be hermetically sealed, internally
isolated, rotary-type, and permanently mounted on rubber
isolators. No removal or adjustment of compressor hold
down bolts is to be required during installation.
Furnish and install air cooled through the wall package terminal air conditioners (heat pumps). Units are certified under
the ARI (American Refrigeration Institute) and CSA (Canadian Standards Association) EEV certification programs and
listed by U. L. (Underwriters Laboratories).
Unit Controls
The unit’s controls must be completely wired and acces-
sible from the top. Controls must include high and low
fan speeds for both cooling, heating, and fan only opera-
tion, and an OFF position. Other unit controls must
include a concealed ventilation control to allow the
introduction of filtered air into the room, a concealed fan
mode switch to allow the owner to preset for either
continuous fan or thermostatically cycled fan operation.
Additionally, the following controls are to be included as
standard on all units:
• Compressor restart delay
• Random restart circuit
• Front desk control
• Automatic freeze protection
• Remote control capability
• Mechanical temperature limiter
• Remote temperature sensing capability
Evaporator/Condenser Fans
Direct drive with a permanent split capacitor two-speed
motor. Condensate must be directed onto the con-
denser coil to aid in evaporation and removal. Con-
denser fan must be propellor type and evaporator fan
must be blower type.
Coils
Unit’s coils must have rifled copper tubing expanded into
rippled-edge louvered aluminum fins.
Air Discharge
Must be a sloped surface so that obstructions cannot be
placed on the unit. Discharge conditioned air can be
directed into the room at an angle of 15 or 40 degrees
from the vertical position. The discharge grille must be
of polycarbonate material to resist bending, cracking,
rusting and corrosion.
Warranty
The warranty is for Full One Year on the entire unit; Full
Second through Fifth Year on the entire sealed refrig-
erant system components; Limited Second through
Fifth Year on functional parts only.
GUIDE SPECIFICATIONS -- Chassis