Tubing Size Torque (Foot-Pounds)
3/8 10
1/2, 5/8, 3/4 14
7/8, 1 1/8 16
After closing the valve bonnet, perform a final refrigerant
leak test on the valves and sweat connections. Return the
room thermostat to the desired settings.
Troubleshooting
(QUALIFIED SERVICER ONLY)
When troubleshooting, the first step should always be to
check for clean coils, clean filter(s), and proper airflow.
Indoor airflow should be 350 to 450 CFM per ton of cooling,
based on the size of the outdoor unit.
If further information is needed, see the Remote Heat
Pump Service Manual or contact your Amana distributor.
Defrost System
This unit is equipped with a time/temperature defrost board.
Defrosting of the outdoor coil is determined by both coil
temperature and compressor run time. Adjustment can be
changed as required. There are 30, 60, and 90 minute
settings available. Adjust only if geographical conditions,
outdoor humidity, or other adverse conditions make it
necessary.
Figure 5
WARNING
To avoid electrical shock or death,
disconnect the power before changing the
defrost time cycle.
If adjustment of the run time appears advisable:
1. Disconnect power to outdoor unit.
2. Move the defrost time adjustment pin from 90 minutes
to 60 minutes or 30 minutes as required (refer to Figure
5).
3. Reconnect the electrical power.
The maximum defrost time is 14 minutes. Most defrost
cycles are shorter.
SERVICING
WARNING
To avoid electrical shock or death,
disconnect the electrical power before
servicing.
When servicing, it may be necessary to rapidly advance the
system through a defrost cycle. To do this:
1. Ensure the 24Vac power is on.
2. Place the defrost time adjustment pin on TEST.
NOTE: If the outdoor coil temperature is above 30°F,
place a jumper wire between the DFS terminals
(defrost sensor) on the defrost control before placing
defrost time adjustment pin on TEST.
3. Reconnect electrical power to outside unit.
4. Place the system into heating operation.
The defrost board function will speed up when the test pins
are connected. Time between defrosts will be 14 seconds.
Defrost time will be 6.5 seconds.
After servicing is completed, disconnect the power, move
the Defrost Time Select Tab back to 30, 60, or 90, remove
jumper wire on DFS, and reconnect the power.
NOTES:
1. If the time select tab remains in TEST position for five
(5) minutes, the control will ignore TEST mode and
assume a normal 90 minute defrost cycle. To over-
ride this, briefly remove and then replace the select
tab.
2. When the unit starts the defrost cycle, quickly re-
move the time select tab to allow normal defrosting
and defrost termination to proceed. The select tab
can be reconnected to TEST to repeat the defrost
cycle, or the tab can be placed in the desired time
setting. (Jumping both test pins with a small insu-
lated screw driver will also work.)