C/D - 4
SPECIFICATIONS
**PTC/H09*A50*C is 2-stage; PTC/H12*A50*C and PTC/H15*A50*D are 1-stage. (Not available on 7,000 BTU models.
Hydronic Heat Models
Hydronic Models / Hot Water & Steam Heating
These special models are shipped without a chassis front,
without electric heat, and have an additional relay and 40VA
transformer for water or steam valve operation. Also avail-
able in Hydronic with Powered Vent and Hydronic with Pow-
ered Door. See Model Identification (right) for Special Fea-
ture Codes for these models. See page C/D-7 for hydronic
accessories.
Hydronic with Manual Door
* Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions.
Electric Heater Performance (PTC and PTH Models)
(
Primary
Heating
for PTC models;
Auxiliary Heating
for PTH models)
ELECTRIC
NOMINAL HEATING
TOTAL TOTAL MIN. CIRCUIT OVERCURRENT
VOLTAGE
HEATER NO. OF BTUH BTUH BTUH WATTS AMPS AMPACITY PROTECTION
POWER
SIZE (kW) STAGES AT 230V AT 208V AT 265V (NOTE 6) (NOTE 8) (NOTE 2) (NOTE 4) CORD
230/208V 2.5/2.0 1 8,500 6,800 - - 2,650/2,140 11.5/10.2 14.2 15 6 - 15 P
230/208V 3.5/2.9 1 12,000 9,900 - - 3,650/3,040 15.8/14.5 19.6 20 6 - 20 P
230/208V 5.0/4.1 ** 17,100 14,000 - - 5,150/4,240 22.3/20.3 27.7 30 6 - 30 P
265V 2.5 1 - - - - 8,500 2,650 10.0 12.4 15 7 - 20 P
265V 3.7 1 - - - - 12,600 3,850 14.6 18.1 20 7 - 20 P
265V 5.0 ** - - - - 17,100 5,150 19.5 24.2 25 7 - 30 P
PTC Models
COOLING/ELECTRIC HEAT
*Engineering Design Level “D” refers to:
PTC153A**AD - PTC154A**AD
PTH153A**AD - PTH154A**AD
PT C 09 3 A 35 A C
C = COOLER
A = Standard Model
H = HEAT PUMP
B = Power Vent
C = Seacoast Model
D = Cond. Disposal Pump
F = Hydronic w/Power Vent & Door
G = Hydronic w/Power Door
07 = 7,000 Btuh H = Hydronic w/Manual Door
09 = 9,000 Btuh J = Power Door
12 = 12,000 Btuh K = Cond. Pump & Power Vent
15 = 15,000 Btuh L = Cond. Pump & Power Door
3=230/208v 60 Hz 1 PH 00 = 0.0 KW
4=265v 60 Hz 1 PH 15 = 1.5 KW
5=240/220v 50 Hz 1 PH 25 = 2.5 KW
35 = 3.5 KW
(265V) Models
50 = 5.0 KW
AMANA C/D MODELS
AMANA C/D MODELS
*
Model Number
Voltage
Capacity
Cooling
Capacity
EER
PTC093A00HC 230/208 9,100 / 8,900 11.3
PTC123A00HC 230/208 12,000 / 11,900 10.7
PTC153A00HD 230/208 14,200/14,000 9.2
PTC094A00HC 265 9,100 11.3
PTC124A00HC 265 12,200 10.7
PTC154A00HD 265 14,200 9.3
Cooling Performance
Model (Basic) (NOTES 1, 7, 9 & 10) PTC073A**AC PTC074A**AC PTC093A**AC PTC094A**AC PTC123A**AC PTC124A**AC PTC153A**AD PTC154A**AD
Voltage
(NOTES 1 & 3)
230/208 265 230/208 265 230/208 265 230/208 265
Capacity (BTUH)
7,100 / 7,000 7,100 9,100/8,900 9,100 12,000 / 11,900 12,000 14,200/14,000 14,200
Amps
2.8/3.0 2.3 3.7/3.8 3.0 4.6/5.0 4.3 6.3/6.9 5.9
Watts
610 / 600 610 805 / 785 805 1,120 / 1,110 1,130 1,500 / 1,480 1,500
EER
11.6 11.6 11.3 11.3 10.7 10.7 9.5 9.5
Unit without Electric Heater
(NOTES 2 & 4)
4.0 3.6 5.1 4.4 6.4 5.7 8.8 7.7
245 / 240 245 245 / 240 245 325 / 315 325 325/315 325
Low
220 / 205 220 220 / 205 220 250 / 229 250 250/220 250
265 / 260 265 265 / 260 265 345 / 335 345 345/335 345
Low
230 / 215 230 230 / 215 230 265 / 235 265 265/235 265
Ventilated Air, CFM (Fan Only)*
65* 65* 65* 65* 70* 70* 70* 70*
Ventilated Air, CFM (Compressor & Fan)*
65* 65* 65* 65* 70* 70* 70* 70*
Dehumidification (Pints/Hr.)
1.6 1.6 2.6 2.6 3.5 3.5 4.4 4.4
Net Weight
(approximate Lbs.)
90 90 95 95 105 105 110 110
Shipping Weight
(approximate lbs.)
105 105 110 110 120 120 125 125
CFM (Cool, Wet Coil) High
CFM (Dry Coil) High