Amana DigiSmart PTC models Especificaciones Pagina 8

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 7
8 www.amana-ptac.com SS-DPTAC
SPECIFICATION SHEET
PTC MODELS — COOLING/ELECTRIC HEAT
Model
1, 7, 9, 10, 12
PTC073B**A- PTC074B**A- PTC093B**AM PTC094B**AM PTC123B**AM PTC124B**AM PTC153B**AM PTC154B**AM
Voltage
1, 3, 11
230/208 265 230/208 265 230/208 265 230/208 265
Capacity
(BTU/h)
M Models
M= 7,100/6,900
M = 7,100 9,100/8,900 9,100
12,000/11,900
12,000
14,000/13,900
14,000
N Models
N= 7,400/7,300
N = 7,300 N/A N/A N/A N/A N/A N/A
Amps
12
2.8/3.0 2.3 3.7/3.8 3.0 4.6/5.0 4.3 6.3/6.9 5.9
Watts
12
610/595 610 790/775 790 1,110/1,100 1,130 1,470/1,450 1,470
EER
M Models M= 11.6/11.6
M = 11.6 11.5 11.5 10.8 10.8 9.5 9.5
N Models N= 12.4/12.8
N = 12.4 N/A N/A N/A N/A N/A N/A
Unit without Electric Heater
Min. Circuit Amps
2, 4, 12
4.0 3.6 5.1 4.4 6.4 5.7 8.8 7.7
CFM
(Cool/Wet Coil)
High 245/240 245 245/240 245 325/315 325 325/315 325
Low 220/205 220 220/205 220 250/229 250 250/220 250
CFM (Dry Coil)
High 265/260 265 265/260 265 345/335 345 345/335 345
Low 230/215 230 230/215 230 265/235 265 265/235 265
Ventilated Air, CFM
(Fan Only)*
65* 65* 65* 65* 70* 70* 70* 70*
Ventilated Air, CFM
(Compressor & Fan)*
65* 65* 65* 65* 70* 70* 70* 70*
Dehumidi cation
(Pints/Hr.)
1.6 1.6 2.6 2.6 3.5 3.5 4.4 4.4
Net Weight (lbs.) 90 90 95 95 105 105 110 110
Shipping Weight (lbs.) 105 105 110 110 120 120 125 125
- Denotes M or N models
*
Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions.
Notes:
All 265-volt models must use an Amana
®
brand sub-base (PTSB4**E) or an Amana
®
brand hard-wire kit (PTPWHWK4).
Minimum Circuit Ampacity (MCA) ratings conform to the Na tion al Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-
style time-delay fuses (included and factory-installed on all Amana
®
brand 265-volt chassis). See heater performance for total MCA.
Heating capacity and ef ciency based on unit operation without condensate pump; unit automatically switches to electric heat
at approximately 24°F outdoor ambient.
Total watts for 12,000 and 15,000 BTU/h models; subtract 70 watts for PT07/09*B**A*
Specify two-digit heater kW size to complete model number.
Total amps for 12,000 and 15,000 BTU/h models; subtract 0.2 amps for PT07/09*B*A*.
R-22 refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to
compressor only.
1–
2–
3–
4–
5–
6–
7–
8–
9–
10–
11–
12–
PRODUCT SPECIFICATIONS