SS-DPTAC www.amana-ptac.com 11
SPECIFICATION SHEET
PTH MODELS — REVERSE-CYCLE HEATING PERFORMANCE
Heating
Capacity
1
PTH073B**A-
PTH074B**A- PTH093B**AM
PTH094B**AM PTH123B**AM PTH124B**AM PTH153B**AM PTH154B**AM
BTU/h
5
M Models
M=6,200/6,000
M = 6,200
8,200/8,000
8,200
10,800/10,600
10,800
13,300/13,200
13,300
N Models
N=6,400/6,300
N = 6,200 N/A N/A N/A N/A N/A N/A
Amps
12
2.6/3.0 2.2 3.2/3.6 2.6 4.5/5.1 3.9 5.7/6.3 5.4
Watts
12
550/530 550 750/730 750 1,020/1,000 1,020 1,34 0/1,330 1,340
COP
5
M Models
M= 3.3/3.3 M = 3.3 3.2 3.2 3.1 3.1 2.9 2.9
N Models
N= 3.5/3.6 N = 3.5 N/A N/A N/A N/A N/A N/A
CFM (Dry) 235/230 235 235/230 230 310/290 310 345/335 345
Heating
(BTU/h)
5
Outdoor
Ambient
Rating
Point
62 °F 7,200/7,000 7,200 9,800/9,600 9,800
13,000/12,800
13,000
15,800/15,700
15,800
57 °F
6,900/6,700
6,900 9,300/9,100 9,300
12,300/12,100
12,300
15,000/14,900
15,000
52 °F
6,500/6,300
6,500
8,700/8,500
8,700
11,600/11,40 0
11,600
14,200/14,100
14,200
47 °F
6,200/6,000
6,200
8,200/8,000
8,200
10,800/10,600
10,800
13,300/13,200
13,300
COP*
3.3/3.3
3.3 3.2/3.2 3.2 3.1/3.1 3.1 2.9/2.9 2.9
42 °F
5,900/5,700
5,900 7,700/7,500 7,700
10,100/9,900
10,100
12,500/12,400
12,500
37 °F
5,600/5,400
5,500 7,200/7,000 7,200 9,400/9,200 9,400
11,70 0/11,60 0
11,70 0
32 °F
5,300/5,100
5,200
6,700/6,500
6,700
8,600/8,400
8,600
10,800/10,700
10,800
27 °F
5,000/4,800
5,000
6,200/6,000
6,200 7,900/7,700 7,900
10,000/9,900
10,000
24 °F
4,800/4,600
4,800
5,900/5,700
5,900 7,500/7,300 7,500 9,500/9,400 9,500
Watts
Outdoor
Ambient
62 °F 580/560 580 810/790 810 1,120/1,10 0 1,120 1,465/1,455 1,465
57 °F 575/555 575 800/780 800 1,090/1,075 1,090 1,440/1,430 1,440
52 °F 555/535 555 775/755 775 1,060/1,0 45 1,060 1,405/1,395 1,405
47 °F 550/530 550 750/730 750 1,020/1,005 1,020 1,340/1,330 1,340
42 °F 540/525 560 730/710 730 985/970 985 1,325/1,315 1,325
37 °F 530/515 545 705/685 705 950/935 950 1,285/1,275 1,285
32 °F 515/500 535 690/670 690 900/885 900 1,240/1,230 1,240
27 °F 505/490 525 660/640 660 855/840 855 1,190/1,180 1,190
24 °F 500/485 520 640/620 640 830/815 830 1,180/1,170 1,180
- Denotes M or N models
See Page 10 for Notes and Auxiliary Electric Heater Performance.
COP = Coeffi ciency of Performance; per ARI Test Procedures, units are rated for capacities and effi ciencies.