Amana GUC Series Manual de instrucciones Pagina 9

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 8
9
tight where it penetrates the roof with a proper flashing
such as used with a plastic plumbing vent. The vent may
be run through an existing unused chimney: however, the
pipe must be used all the way through to at least 12 inches
above the top of the existing chimney. The space between
the vent pipe and the chimney must be closed with a
weather tight, corrosion resistant flashing.
Never vent with
an existing appliance or vent used by a solid fuel appliance.
WARNING
Upon completion of the furnace installation,
carefully inspect the entire flue system
both inside and outside the furnace to
assure it is properly sealed. Leaks in the
flue system can result in serious personal
injury or death due to exposure to flue
products, including carbon monoxide.
CANADIAN VENTING REQUIREMENTS
In Canada, venting shall conform to the requirements of
the current CANI-B149 Installation Codes.
Use only C.S.A. Listed 2 inch or 3 inch nominal diameter
PVC or ABS pipe and fittings throughout.
The Minimum vent consists of 3 feet of straight pipe with
2 elbows (9 equivalent feet).
A single wall vent shall not be run vertically through the
roof. The vent may be run through an existing unused
chimney as described in the previous venting section
provided the space between the vent pipe and the
chimney is insulated and closed with a weather tight,
corrosion resistant flashing.
Cut all vent pipe at right angles. Remove inside and
outside burr at each cut. Use cleaner to clean pipe and
fitting socket. Use CSA listed cement to fasten pipe and
fittings.
Follow manufacturers cleaning and cementing instruc-
tions carefully to avoid leakage.
Note: All piping exposed outdoors or in unheated areas
must be insulated with 1/2 inch thick closed cell foam
insulation such as “armaflex” or “insultube”.
The vent terminal shall
not
be located:
1. Less than 12 inches above the finished grade line.
2. Less than 36 inches from any building opening or any
gas service regulator. (For gas service regulators in
the Province of Ontario, 72 inches.)
3. Less than 72 inches from the combustion air inlet of
another appliance.
4. Directly above a gas utility meter or service regulator.
5. Over a walkway unless 84 inches above grade.
VI. Combustion Air and Vent Piping
(GUD - Two Pipe)
GENERAL INFORMATION AND SAFETY
PRECAUTIONS
WARNING
Failure to follow these instructions can
result in bodily injury or death from
asphyxiation. Therefore, carefully read and
follow all instructions given in this section.
CAUTION
Terminate the combustion air intake as far
as is practical from the air conditioning
unit or heat pump, swimming pools,
swimming pool pumping units, and dryer
vents.
All combustion air and exhaust piping must be installed in
accordance with local codes and these instructions.
When the furnace is installed in a confined space where
the minimum clearances to combustible surfaces (see
Specification Sheet) are applied, such as in a closet or a
utility room, two ventilation openings are required with a
total minimum free area of 0.25 square inches per 1,000
BTUH of the furnace input rating. One opening must be
within 12 inches of the top and one must be within 12
inches of the bottom of the confined space. In typical
construction, the clearance between the door and door
frame will usually be adequate to satisfy this ventilation
requirement.
When the GUD furnace is installed in the same space with
other gas appliances, such as a water heater, make sure
there is an adequate supply of combustion and ventilation
air for the other appliances. See the latest edition of the
National Fuel Gas Code NFPA 54/ANSI Z223.1. for deter-
mining the combustion air requirements for the appli-
ances.
The GUD furnaces are supplied with a 3 inch air intake
terminal screen. This screen is shipped in the same plastic
sack that held this manual. For both vertical and horizontal
installations, insert the screen into the air intake terminal
until it is firmly secured at the hub of the terminal elbow.
If the vent (flue) pipe is exposed to extremely cold tempera-
tures and/or long runs through unheated spaces or out-
doors, insulation may be required on the outside of the vent
pipe to prevent condensate from freezing. Canadian in-
stallers must take note of the “Canadian Venting Require-
ments” in this section. Where required, use 1/2 inch thick
closed cell foam insulation such as Armaflex or Insultube.
Note: Inspect the flue for leaks before installing any
insulation.
If the combustion air pipe is to be installed above a
suspended ceiling or other area where dripping of conden-
sation will be objectionable, insulation of the combustion
air pipe may be required. Where required, use 1/2 inch
Vista de pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 27 28

Comentarios a estos manuales

Sin comentarios