New installaons typically require a minimum of WS900D wall sleeve and an outdoor grille.
WAll sleeves (Ws900e)
The wall sleeve must be industry-accepted dimensions:
14⅛” depth x 42” width x 16¹/
₁₆
” height and constructed of
G90 HDG galvanized steel with a baked corrosion-inhibing
urethane primer and baked-polyester topcoat enamel.
Sleeve must be insulated and shipped with a weather
resistant rear closure panel installed.
ouTdoor grilles
Outdoor grille must be architecturally extruded, louvered
aluminum (AGK01*B), one-piece polymer-blend injecon
molded louver (PGK01*B) or standard stamped aluminum
(SGK**B). All other grilles must be submied to the PTAC
manufacturer for feasibility, airow characteriscs and
compliance with UL regulaons, where necessary.
The oponal accessories listed below perform specic funcons required in some installaons.
CondensATe drAin KiT (dK900d)
Aaches to the boom of the wall sleeve for direconal-
controlled internal or external disposal of condensate,
defrost or rain water.
subbAse KiT (PTsb***e)
Necessary for UL lisng requirements for 265V units (Hard
Wire Kit may be substuted for Subbase kit). Oponal for
230/208V units. Must be pre-wired to facilitate eld-electrical
connecons and include an NEMA 6 or 7 conguraon
electrical receptacle. It must have two leveling screws for
sleeve support and accurate unit leveling during installaon.
Locaons for eld installaon of physical disconnect
switches, cartridge-style fuse holders and circuit breakers
must be provided. Side-skirts must be provided with sub-
bases. (PTSB000E Non-Electrical Subbase available.)
PoWer venT & dAmPer
Must be provided to maximize venlaon air intake to up to
approximately 95 CFM. Power vent must be o and damper
door closed when unit fan is de-energized.
fuse Holder (inCluded in 265v CHAssis)
Must be installed either in the unit or the subbase and must
match the electrical requirements of the chassis.
seCuriTy Key loCKs (Kl03e)
Must be installed to prevent tampering of the unit controls.
Unit room cabinet must also be secured to the chassis with
eld supplied screws. UL-approved for instuonal use only.
disConneCT sWiTCH
Power disconnect switch must be installed in subbase for
use as a physical disconnect, where required by local codes.
duCT KiTs (mdK01e, edK02b, TdK02b, PTdK01e, ddK01e)
Three kits must be supplied to provide ducted, condioned
air into a second room: a main duct kit, an extension duct kit
and a terminal duct kit.
HydroniC HeAT KiT
Is required for heang funcons instead of electric resistance
heaters. Unit must retain complete service access with the
kit installed. Proper water or steam valves must be used.
CondensATe removAl PumP (HeAT PumPs only)
Must be installed to assist in removing the condensate
developed by the heat pump operaon and transfer it to the
indoor coil to dissipate into the room, adding humidity to
the room.
CirCuiT breAKer KiT
Must be installed in subbase to provide overcurrent
protecon for proper 230/208V amperage. Can also be
used as a physical disconnect where local codes permit for
230/208 voltage.
HArd Wire KiT
Must be used to permanently wire chassis for hard wire
purposes. (For 265V units, Hard Wire Kit may be substuted
with Subbase Kit.)
THermosTATs
A manufacturer-approved manual, auto changeover or
programmable tradionally wired thermostat must be
installed to provide full remote operaon of the chassis. A
Remote Escutcheon Kit must be used to indicate remote
operaon.