Amana CKF60 Instrucciones de operaciones Pagina 3

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 12
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 2
3
Heat pumps require special location consideration in areas
of heavy snow accumulation and/or areas with prolonged
continuous subfreezing temperatures. Heat pump unit bases
are cutout under the outdoor coil to permit drainage of frost
accumulation. Units must be situated to permit free unob-
structed drainage of the defrost water and ice. A minimum
7.6 cm clearance under the outdoor coil is required in the
milder climates.
In more severe weather locations, it is recommended that
units be elevated to allow unobstructed drainage and air flow.
While there are no hard and fast rules regarding elevation, we
suggest the following minimums:
If the outdoor unit is mounted above the air handler, the
maximum lift should not exceed 21.3 m (suction line). If air
handler is mounted above condensing unit, the lift should not
exceed 15.2 m (liquid line).
-
INSTALLATION, ELECTRICAL
The supply power, voltage, frequency and phase must coincide
with that on unit nameplate. All wiring should be carefully
checked against the manufacturer’s diagrams. Field wiring
must be connected in accordance with the National Electric
Code or other local codes that may apply. Make certain that
the equipment is adequately grounded per local code re-
quirements.
The manufacturer bears no responsibility for damage caused
to equipment or property as a result of the use of larger than
recommended size protective devices as listed on the unit
rating plate.
This equipment has been started at minimum rated voltage
and checked for satisfactory operation. Do not attempt to
operate this unit if available voltage is not within the minimum
and maximum shown on nameplate.
NOTE: Units are shipped without refrigerant and are
pressurized with a nitrogen holding charge of 125 PSI.
This charge must be removed and unit evacuated and
charged as per the installation instructions. Release holding
charge by opening the suction valve first then the liquid line
valve before attaching and brazing lines. When opening
valves with retainers, open each valve only until the top of the
stem is 1/8" from the retainer. To avoid loss of refrigerant, DO
NOT apply pressure to the retainer. When opening valves
without a retainer remove service valve cap and insert a hex
wrench into the valve stem and back out the stem by turning
the hex wrench counterclockwise. Open the valve until it
contacts the rolled lip of the valve body.
NOTE: These are not back-seating valves. It is not necessary
to force the stem tightly against the rolled lip.
Insulation of at least 1.3 cm wall thickness should be used on
the suction line to prevent condensation when cooling and
heat loss when heating. The insulation should be installed on
the tubing prior to installation and should be run the entire
length of the installed line. The end of the tubing over which
the insulation is being slipped should be covered to insure
that no foreign material is introduced to the interior of the
tubing. The outdoor units are equipped with two service
valves, and, “as shipped”, the valves are in the front-seated
or “closed” position.
The indoor coil is pressurized; the copper cap must be
punctured to permit a gradual escape of the pressure prior to
un-sweating those caps. Immediately couple the tubing to
the indoor unit to minimize exposing the coils to moisture.
REFRIGERANT LINE CONNECTIONS
IMPORTANT
To avoid overheating the service valves or expansion device
while brazing, wrap the component with a wet rag, or use a
thermal heat trap compound. Be sure to follow the
manufacturer’s instruction when using the heat trap com-
pound.
NOTE: Remove Schrader valves from service valves before
brazing tubes to the valves. Use a brazing alloy of 2%
minimum silver content. Do not use flux. Torch heat required
to braze tubes of various sizes is proportional to the size of
the tube. Tubes of smaller size require less heat to bring the
tube to brazing temperature before adding brazing alloy.
Applying too much heat to any tube can melt the tube. Service
personnel must use the appropriate heat level for the size of
the tube being brazed.
NOTE: The use of a heat shield when brazing is recom-
mended to avoid burning the serial plate or the finish of the
unit.
Vista de pagina 2
1 2 3 4 5 6 7 8 ... 11 12

Comentarios a estos manuales

Sin comentarios